Fluke 437 Series II 400 Hz Basic Power Quality and Energy Analyzer Fluke 437 Series II 400 Hz Basic Power Quality and Energy Analyzer Designed for capturing power quality measurements in avionic and military systems, Fluke 437 Series II is the must-have 400 Hz quality analyzer. P000249 Power Quality Analyzers 0 VND Quantity: 1 Cái


  •  
  • Fluke 437 Series II 400 Hz Basic Power Quality and Energy Analyzer

  • Post on 23-09-2015 10:01:02 AM - 1094 Views
  • Price: Contact

  • Designed for capturing power quality measurements in avionic and military systems, Fluke 437 Series II is the must-have 400 Hz quality analyzer.


Quantity
Locating, Predicting, Preventing and Troubleshooting Power Quality Issues – Up to 400 Hz

Higher power frequencies mean smaller and lighter transformers and motors – a critical concern in avionic and military transport applications where weight is a primary concern. Designed specifically for these environments, the Fluke 437 Series II Power Quality and Energy Analyzer is a must-have for those working in ships, submarines, aircraft, spacecraft and other military vehicles. 

Equipped with all the functionalities of the Fluke 435 Series II, the 437 Series II offers the best in power quality and energy analysis all the way to 400 Hz.
 
Product Specifications
Volt Model Measurement Range Resolution Accuracy
Vrms (AC + DC) 1 V to 1000 V phase to neutral 0.01 V ±0.1% of nominal voltage4
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%
Vfund   0.1 V ±0.1% of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC) i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1 mV/A 1x 5 A to 2000 A 1A ±0.5% ±5 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Apk i430-Flex 8400 Apk 1 Arms ±5%
1 mV/A 5500 Apk 1 Arms ±5%
A Crest Factor (CF) 1 to 10 0.01 ±5%
Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts
1 mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts
Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts 
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1 mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
1 mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Hz
Fluke 437 @ 50 Hz nominal 42.500 Hz to 57.500 Hz 0.001 Hz ±0.01 Hz
Fluke 437 @ 60 Hz nominal 51.000 Hz to 69.000 Hz 0.001 Hz ±0.01 Hz
Fluke 437 @ 400 Hz nominal 340.0 Hz to 460.0 Hz 0.1 Hz ±0.1 Hz
Power
Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts
Power Factor (Cos j/DPF)   0 to 1 0.001 ±0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 1000 V 0.1 V ±5% 1
THD 0.0% to 100% 0.1% ±2.5%
Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts
THD 0.0% to 100% 0.1% ±2.5%
Watts % f or r 0.0% to 100% 0.1% ±n x 2%
Absolute Depends on clamp scaling and V nominal ±5% ±n x 2% ±10 counts
THD 0.0% to 100% 0.1% ±5%
Phase Angle -360° to +0° ±n x 1°
Flicker
Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%
Unbalance
Volts % 0.0% to 20.0% 0.1% ±0.1%
Amps % 0.0% to 20.0% 0.1% ±1%
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
Relative V % 0% to 100% 0.10% ±0.4%
Absolute V 3 s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage
General Specifications
Case Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2
Display Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated
Memory 8 GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-Time Clock Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Environmental
Operating Temperature 0°C ~ +40°C; +40°C ~ +50°C excl. battery
Storage Temperature -20°C ~ +60°C
Humidity +10°C ~ +30°C: 95% RH non-condensing 
+30°C ~ +40°C: 75% RH non-condensing 
+40°C ~ +50°C: 45% RH non-condensing
Maximum Operating Altitude Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V 
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V 
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility (EMC) EN 61326 (2005-12) for emission and immunity
Interfaces Mini-USB-B, Isolated USB port for PC connectivity SD card slot accessible behind instrument battery
Warranty Three years (parts and labor) on main instrument, one year on accessories
     

 