Fluke 985 Particle Counter Fluke 985 Particle Counter Particle counter from Fluke to test and analyze indoor air quality P000158 HVAC IAQ 0 VND Quantity: 1 Cái


  •  
  • Fluke 985 Particle Counter

  • Post on 22-09-2015 04:20:21 PM - 1308 Views
  • Price: Contact

  • Particle counter from Fluke to test and analyze indoor air quality


Quantity
  • Take a new look at indoor air quality.

    The Fluke 985 Particle Counter is the preferred choice for HVAC and IAQ professionals. From filter testing to IAQ investigations, the Fluke 985 is the portable solution for determining airborne particle concentrations. Use the Fluke 985 to immediately respond to occupant complaints, or as part of a comprehensive preventive maintenance program.

    With the Fluke 985 you can:

    • Measure filter efficiency
    • Monitor industrial cleanrooms
    • Pre-screen indoor air quality and confidently work with IAQ specialists
    • Locate particle sources for remediation
    • Report the effectiveness of repairs to customers
    • Drive additional business by demonstrating the need for maintenance and repair

    With a large screen, intuitive icons for navigation and on-screen data presentation, the Fluke 985 allows users to run more tests quickly, with less time spent cycling through screens to obtain the data. The Fluke 985 is lightweight and easy to use in any position and with easy data export options using USB cable, memory stick it’s easy to review and analyze the data anywhere and anytime.

    Measured Specifications
    Channels 0.3 μm, 0.5 μm, 1.0 μm, 2.0 μm, 5.0 μm, 10.0 μm
    Flow rate 0.1 cfm (2.83 L/min)
    Light source 775 nm to 795 nm, 90 mW class 3B laser
    Count modes Raw counts, #/m3, #/ft3, #/liter in Cumulative or Differential mode
    Counting efficiency 50% @ 0.3 μm; 100% for particles > 0.45 μm (per ISO 21501)
    Zero count 1 count / 5 minute (JIS B9921)
    Concentration limits 10% at 4,000,000 particles per ft3 (per ISO 21501)
    Data storage 10,000 records (rotating buffer)
    Alarms Counts, low battery, sensor fail
    Delay time 0 to 24 hours
    Sample inlet Isokinetic probe
    Security Administrator password control (optional)
    Communication mode USB or Etheret
    Dimensions (L x W x D) 27.2 x 9.9 x 5.3 cm (10.7 x 3.9 x 2.1 in)
    Weight 0.68 kg (1.5 lb)
    Power adapter 100 V AC to 240 V AC, 12 V DC, 2.5 A
    Rechargeable battery Li-ion 7.4 V 2600 mAh; 10 hours typical use (5 hours continuous sampling) / 3.5 hours
    Calibration PSL particles in air (NIST traceable)
    Operating environment 50°F to 104°F (10°C to 40°C) / < 95% non-condensing relative humidity
    Storage environment 14°F to 122°F (-10°C to 50°C)/Up to 98% non-condensing relative humidity
    Warranty One-year
    Accessories included Cradle for charging and convenient USB and Ethernet communications, ENET CAT5E 7 foot cable, USB-A to MINI-B 6 foot cable, 12 V dc power supply, zero count inlet- filter, filter adapter, sample inlet protective cap, hard case, getting started manual and users manual CD
     

 