Price: Contact
Fluke 376 AC/DC clamp meters provide increased display flexibility and improved wire access. Learn more about expanding your range of measurement today!
Expand Your Measurement Range with Increased Flexibility
You can measure around awkward sized conductors with the Fluke 376 True RMS Clamp Meter with iFlex®, expanding your measurement range to 2500 A AC. With True RMS voltage and current measurements, the Fluke 376 can read up to 1000 V and 1000 A in both AC and DC modes.
The Fluke 376 is the direct replacement for the Fluke 337 Clamp Meter.
Safety Conformance
EN/IEC 61010-1:2001; 1000V CAT III, 600V CAT IV.
Electrical Specifications | ||||
AC Current via Jaw | ||||
Range | 374 and 375 376 | 600.0 A 999.9 A | ||
Resolution | 0.1 A | |||
Accuracy | 2% ± 5 digits (10-100 Hz) 2.5% ± 5 digits (100-500 Hz) | |||
Crest Factor (50/60 Hz) | 3 @ 500 A (375 and 376 only) 2.5 @ 600 A 1.42 @1000 A (376 only) Add 2% for C.F. > 2 | |||
AC Current via Flexible Current Probe | ||||
Range | 2500 A | |||
Resolution | 374 and 375 | 0.1 A (≤ 600 A) 1 A (≤ 2500 A) | ||
376 | 0.1 A (≤ 999.9 A) 1 A (≤ 2500 A) | |||
Accuracy | 3% ±5 digits (5 – 500 Hz) | |||
Crest Factor (50/60Hz) | 3.0 at 1100 A (375 and 376 only) 2.5 at 1400 A 1.42 at 2500 A Add 2% for C.F. > 2 | |||
Distance from Optimum | i2500-10 Flex | i2500-18 Flex | Error | |
![]() | A | 0.5 in (12.7 mm) | 1.4 in (35.6 mm) | ± 0.5% |
B | 0.8 in (20.3 mm) | 2.0 in (50.8 mm) | ± 1.0% | |
C | 1.4 in (35.6 mm) | 2.5 in (63.5 mm) | ± 2.0% | |
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. | ||||
DC Current | ||||
Range | 374 and 375 376 | 600.0 A 999.9 A | ||
Resolution | 0.1 A | |||
Accuracy | 2% ± 5 digits | |||
AC Voltage | ||||
Range | 374 and 375 376 | 600.0 V 1000 V | ||
Resolution | 374 and 375 376 | 0.1 V 0.1 V (≤ 600.0 V) 1 V (≤ 1000 V) | ||
Accuracy | 1.5% ± 5 digits (20 – 500 Hz) | |||
DC Voltage | ||||
Range | 374 and 375 376 | 600.0 V 1000 V | ||
Resolution | 374 and 375 376 | 0.1 V 0.1 V (≤ 600.0 V) 1 V (≤ 1000 V) | ||
Accuracy | 1% ± 5 digits | |||
mV dc | ||||
Range | 375 and 376 | 500.0 mV | ||
Resolution | 0.1 mV | |||
Accuracy | 1% ± 5 digits | |||
Frequency via Jaw | ||||
Range | 375 and 376 | 5.0 - 500.0 Hz | ||
Resolution | 0.1 Hz | |||
Accuracy | 0.5% ± 5 digits | |||
Trigger Level | 5 – 10 Hz, ≥10 A | |||
10 – 100 Hz, ≥5 A | ||||
100 – 500 Hz, ≥10 A | ||||
Frequency via Flexible Current Probe | ||||
Range | 375 and 376 | 5.0 - 500.0 Hz | ||
Resolution | 0.1 Hz | |||
Accuracy | 0.5% ± 5 digits | |||
Trigger Level | 5 – 20 Hz, ≥ 25 A | |||
20 – 100 Hz, ≥ 20 A | ||||
100 – 500 Hz, ≥ 25 A | ||||
Resistance | ||||
Range | 374 375 and 376 | 6000 Ω 60 kΩ | ||
Resolution | 374 | 0.1 Ω (≤ 600 Ω) 1 Ω (≤ 6000 Ω) | ||
375 and 376 | 0.1 Ω (≤ 600 Ω) 1 Ω (≤ 6000 Ω) 10 Ω (≤ 60 kΩ) | |||
Accuracy | 1% ± 5 digits | |||
Capacitance | ||||
Range | 1000 μF | |||
Resolution | 0.1 μF (≤ 100 μF) 1 μ F (≤ 1000 μF) | |||
Accuracy | 1% ± 4 digits | |||
Mechanical Specifications | ||||
Size (L x W x H) | 246 mm x 83 m x 43 mm | |||
Weight | 388 g | |||
Jaw Opening | 34 mm | |||
Flexible Current Probe Diameter | 7.5 mm | |||
Flexible Current Probe Cable Length (head to electronics connector) | 1.8 m | |||
Environmental Specifications | ||||
Operating Temperature | 10°C – +50°C | |||
Storage Temp | -40°C – +60°C | |||
Operating Humidity | Non condensing (< 10 –°C) ≤ 90% RH (at 10°C – 30°C) ≤ 75% RH (at 30°C – 40°C) ≤ 45% RH (at 40°C – 50°C) | |||
Operating Altitude | 3000 meters | |||
Storage Altitude | 12,000 meters | |||
EMC | EN 61326-1:2006 | |||
Temperature Coefficients | Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C | |||
Safety Specifications | ||||
Safety Compliance | CAN/CSA-C22.2 No. 61010-1-04 ANSI/UL 61010-1:2004 ANSI/ISA-61010-1 (82.02.01):2004 EN/IEC 61010-1:2001 to 1000V Measurement Category (CAT) III 600V Measurement Category (CAT) IV Pollution Degree 2 EN/IEC 61010-2-032:2002 EN/IEC 61010-031:2002+A1:2008 | |||
Agency Approvals | ||||
Batteries | 2 AA, NEDA 15A, IEC LR6 |