Fluke 360 AC Leakage Current Clamp Meter Fluke 360 AC Leakage Current Clamp Meter Fluke 360 AC current clamp meter allows you to perform tests without any downtime thereby saving time and helps in maintaining the quality of your equipment. P000071 Clamp Meters 0 VND Quantity: 1 Cái


  •  
  • Fluke 360 AC Leakage Current Clamp Meter

  • Post on 22-09-2015 02:50:23 PM - 927 Views
  • Price: Contact

  • Fluke 360 AC current clamp meter allows you to perform tests without any downtime thereby saving time and helps in maintaining the quality of your equipment.


Quantity
  • The Fluke 360 leakage tester is a rugged and accurate solution for leakage current measurement.

    Ideally designed for non-invasive checks of insulation condition, the Fluke 360 leakage meter allows you to perform tests without powering down the installation or disconnecting equipment - saving you time, without compromising on quality or safety.

    The unique jaw design of the Fluke 360 AC Leakage Current Clamp Meter eliminates the influence of adjacent current conductors, and minimizes the effects of external magnetic fields, even at low currents. This allows you to perform accurate and reliable tests in today’s crowded electrical environments. The tough and high-quality jaw design of the Fluke 360 leakage tester guarantees high stability for long-term repeatability and durability.

    Why leakage current testing?

    Leakage currents can be an indicator of the effectiveness of insulation on conductors. High levels of leakage current may be present in circuits where either the insulation resistance is low, or electronic equipment with filters is used. Leakage currents can cause disruptions of the normal operation of equipment and installations. It is possible to locate the source of leakage currents by using the Fluke 360 leakage current clamp meter and taking methodical measurements throughout the installation. The big advantage of leakage current testing versus insulation testing is that the installation and equipment do not need to be powered down but can be done during normal operation.

     

    General Specifications
    Method of detection Mean value
    Display Digital display 3200 counts
    Bar-graph display 32 segments, LCD
    Measurement cycle 2 times/second (digital display), 12 times/second (bar-graph display)
    Range switching Auto-range
    Ambient temperature and humidity 0°C to 50°C, 80% RH or less (no condensation)
    Temperature coefficient 0.05% of range/°C or less (within the ranges of 0°C to 18°C and 28°C to 50°C for measurement of 0-50 A)
    Influence of external magnetic field 0.0005% typical
    Influence of conductor position Within accuracy
    Circuit voltage < 300 V rms
    Safety standard EN 61010-1, EN 61010-2-032, 300 V CAT III, Pollution Degree 2
    Withstanding voltage 3.7 kV ac
    Battery type 1 x 3 V Lithium battery (button cell) CR2032
    Battery life Approx. 90 hours (when continuously used)
    Auto power-off Approx. 10 minutes
    Diameter of measurable conductor 40 mm max.
    Weight 200 g
    Dimension 176 mm x 70 mm x 25 mm
    Operating altitude 2000 m
    Electrical Specification
    Specifications at 23 ± 5ºC, 80% RH max
    Accuracy (% readout + value of least significant digit)
    3 mA Resolution 0.001 mA
    Accuracy 1% + 5
    Max permissible current 60 A rms
    30 mA Resolution 0.01 mA
    Accuracy 1% + 5
    Max permissible current 60 A rms
    30 A Resolution 0.01 A
    Accuracy % + 5
    Max permissible current 60 A rms
    60 A Resolution 0.1 A
    Accuracy 5% + 5
    Max permissible current 60 A rms
    Mean value detection and RMS-value calibration Accuracy specified at 50/60 Hz
     

 