Quantity
  • Reduced testing complexity, a simplified workflow and an intuitive user interface provide a new level of ease-of-use in battery testing.

    • The ideal test tool for maintenance, troubleshooting and performance testing of individual stationary batteries and battery banks used in critical battery back-up applications
    • The intuitive user interface, compact design and rugged construction ensure optimum performance, test results and reliability
    • Covers a broad range of battery test functions ranging from DC voltage and resistance tests to full condition testing using automated string function testing and the test probe integrated infra-red temperature measurement system
    • Designed for measurements on stationary batteries of all types.
  • Functions Range Resolution Accuracy BT510 BT520 BT521
    Battery Resistance / Strap Resistance1 3 mΩ 0.001 mΩ 1% + 8
    30 mΩ 0.01 mΩ 0.8% + 6
    300 mΩ 0.1 mΩ 0.8% + 6
    3000 mΩ 1 mΩ 0.8% + 6
    VDC 6 V 0.001 V 0.09% + 5
    60 V 0.01 V 0.09% + 5
    600 V 0.1 V 0.09% + 5
    1000 V 1 V 0.09% + 5    
    VAC (45 Hz to 500 Hz with 800 Hz filter) 600 V 0.1 V 2% + 10
    Frequency (displayed with VAC and AAC)2 500 Hz 0.1 Hz 0.5% + 8
    AC voltage ripple (20 KHz  Max) 600 mV 0.1 mV 3% + 20
    6000 mV 1 mV 3% + 10
    ADC/AAC (with accessory Fluke i410) 400 A 1 A 3.5% + 2    
    Temperature 0°C to 60°C 1°C 2°C (4°F)    
    Meter mode 999 records for each measurement position with time stamp
    Sequence mode Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp
    1. The measurement is based on AC injection method. The injected source signal is < 100 mA, 1 kHz.
    2. Trigger level VAC: 10 mV, AAC: 10 A
    Measurement Modes BT510 BT520 BT521      
    Resistance (mΩ)      
    Battery voltage      
    Voltage DC      
    Voltage AC and frequency  (Hz)      
    Ripple volt      
    Temperature of negative battery post          
    DC and AC current (and frequency)          
    DMM mode      
    Sequence mode        
    Discharge measurement mode      
    Automatic measurement  save      
    Wireless commumcation          
    Memory view      
    General Specifications
    Size (H x W x D) 22 x 10.3 x 5.8 cm (9 x 4 x 2 in)
    Weight 850 g (1.9 lb)
    Screen dimensions 7.7 x 5.6 cm (3 x 2.2 in)
    Interface USB mini
    Warranty 3 years
    Environment Specifications
    Operating temperature 0°C to 40°C
    Storage temperature -20°C to 50°C
    Lithium-ion  battery charging temperature 0°C to 40°C
    Operating humidity Non-condensing (10°C)
    ≤ 80% RH (at 10°C to 30°C)
    ≤ 75% RH (at 30°C to 40°C)
    Operating altitude Sea level to 2000 meters
    Storage altitude Sea level to 12,000 meters
    IP rating IP40
    Radio FCC Class A
    Vibration  requirements MIL-PRF-28800F: Class 2
    Drop test  requirements 1 meter
    Temperature coefficients Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C
    Safety  compliance 600 V CAT III
    EMC IEC 61326
    ROHS China, Europe
    Protection class 2 Pollution Degree II
    Battery compliance UN38.3
    UL2054
    IEC62133
    2 G per IEC68-2-26, 25 G, and 29
     

 